KYN28-12中置(zhi)櫃(gui)是(shi)按(an)照(zhao)GB3906-91中(zhong)規定(ding)的鎧裝移開式設計、制(zhi)造(zao)的。外(wai)殼的防護(hu)等(deng)級為(wei)IP4X,中(zhong)置(zhi)櫃(gui)所(suo)用(yong)真空(kong)斷(duan)路器(qi)為(wei)移開式高壓真(zhen)空(kong)斷(duan)路器(qi)。今天小(xiao)編給大(da)家(jia)講(jiang)講移開式真空(kong)斷(duan)路器(qi)安(an)裝使(shi)用(yong)過程(cheng)中應(ying)註意(yi)的細(xi)節。
中(zhong)置(zhi)櫃(gui)櫃(gui)體
KYN28A-12中置(zhi)櫃(gui)的櫃(gui)體是(shi)裝配(pei)式(shi)結構,主要(yao)構件(jian)是(shi)用(yong)敷(fu)鋁(lv)鋅(xin)鋼板(ban),經(jing)CNC數控(kong)機(ji)床加(jia)工(gong)而(er)成。采(cai)用(yong)了(le)多重折(zhe)彎工(gong)藝(yi)和(he)拉鉚螺母(mu)、高(gao)強度(du)螺栓,使(shi)KYN28A-12中置(zhi)櫃(gui)在保(bao)證(zheng)足夠(gou)強度(du)和(he)剛性的同時,重(zhong)量(liang)更輕(qing),抵(di)禦有害氣體腐蝕的能力(li)更(geng)強,而(er)且外(wai)觀更加(jia)美(mei)觀(guan)。中(zhong)置(zhi)櫃(gui)按(an)結構可(ke)分(fen)為(wei)小(xiao)車(che)室(shi)、主母線(xian)室,電纜室
( 電流互(hu)感(gan)器室(shi))和(he)繼電器室(shi) 。除(chu)了(le)繼電器室(shi)以(yi)外(wai),其(qi)余(yu)各個隔室均設置(zhi)通向(xiang)櫃(gui)頂的事故(gu)排(pai)氣通道(dao)。
小(xiao)車(che)室(shi)安(an)裝手(shou)車(che)式(shi)真空(kong)斷(duan)路器(qi),底部(bu)設(she)有小(xiao)車(che)軌(gui)道,供斷(duan)路器(qi)在櫃(gui)內(nei)運(yun)動。隔室內(nei)安(an)裝有主回(hui)路(lu)靜(jing)觸頭的觸頭盒(he)與主母線(xian)室(shi)和(he)電纜室相通。當(dang)小(xiao)車(che)在試(shi)驗(yan)位(wei)置(zhi)或(huo)退出櫃(gui)外(wai)時,活動簾板將靜(jing)觸頭蓋住,形(xing)成有效隔離;當小(xiao)車(che)從(cong)試(shi)驗(yan)位(wei)置(zhi)向(xiang)工(gong)作(zuo)位(wei)置(zhi)移動時(shi),活(huo)動(dong)簾(lian)板自動打開,保證(zheng)主(zhu)回(hui)路(lu)順利(li)連接(jie)。上、下活(huo)動簾(lian)板是(shi)獨(du)立(li)運(yun)動的,並且可(ke)以(yi)分別鎖定(ding)。因(yin)此,如果(guo)需要(yao)的話,檢(jian)修(xiu)人員(yuan)可(ke)以(yi)鎖定(ding)帶(dai)電側(ce)的簾板(ban),檢(jian)修另壹側(ce)的主回(hui)路(lu)靜(jing)觸頭。
小(xiao)車(che)
根(gen)據小(xiao)車(che)上配置(zhi)的主回(hui)路(lu)元件(jian)的不同,主要(yao)有斷(duan)路器(qi)小(xiao)車(che)、電壓互(hu)感(gan)器小(xiao)車(che)(PT小(xiao)車(che)),隔離小(xiao)車(che)和(he)計
量小(xiao)車(che)等(deng)。各類(lei)小(xiao)車(che)按(an)模數(shu)積木式(shi)變(bian)化,同規格(ge)小(xiao)車(che)保(bao)證(zheng)互(hu)換(huan)。小(xiao)車(che)在櫃(gui)內(nei)有試驗(yan) (斷(duan)開)位置(zhi)和(he)工(gong) 作(zuo)位(wei)置(zhi)兩(liang)個定(ding)位(wei)位(wei)置(zhi)。小(xiao)車(che)的推進(退出) 采(cai)用(yong)蝸輪(lun)
副省(sheng)力(li)機(ji)構,操作(zuo)輕便,靈活(huo)。小(xiao)車(che)移出櫃(gui)外(wai)時,需要(yao)配置(zhi)專(zhuan)用(yong)的轉(zhuan)運(yun)小(xiao)車(che)。
小(xiao)車(che)用(yong)轉(zhuan)運(yun)小(xiao)車(che)運(yun)入櫃(gui)體後(hou),首(shou)先定(ding)位(wei)於(yu)試(shi)驗(yan)
(斷(duan)開)位置(zhi),小(xiao)車(che)與(yu)櫃(gui)體鎖定(ding)後(hou),可(ke)以(yi)搖動(dong)推進機構,將小(xiao)車(che)推向(xiang)工(gong)作(zuo)位(wei)置(zhi)。小(xiao)車(che)到(dao)達(da)工(gong)作(zuo)位(wei)置(zhi)時(shi),搖把(ba)搖動(dong)受(shou)阻(zu),小(xiao)車(che)到(dao)位。小(xiao)車(che)的相關(guan)聯(lian)鎖機構保證(zheng)只(zhi)有斷(duan)路器(qi)處(chu)於分(fen)閘狀態,小(xiao)車(che)方(fang)可(ke)移動,只(zhi)有小(xiao)車(che)在試(shi)驗(yan)
(斷(duan)開) 位置(zhi)或(huo)工(gong)作(zuo)位(wei)置(zhi)定(ding)位(wei)後(hou),斷(duan)路器(qi)方可(ke)合閘。
母(mu)線(xian)的安(an)裝
中(zhong)置(zhi)櫃(gui)中(zhong)的母線(xian)均采用(yong)分段(duan)矩(ju)形(xing)母線,在安(an)裝時(shi)必(bi)須(xu)按(an)照(zhao)下(xia)列步(bu)驟進(jin)行:
●可(ke)清(qing)潔幹燥(zao)的軟布將母線擦試幹凈,檢(jian)查(zha)熱縮管(guan)或硫化塗(tu)覆(fu)表面(mian)是(shi)否(fou)有缺(que)陷(xian),在連(lian)接(jie)部(bu)位(wei)塗(tu)上導電膏或(huo)中(zhong)性凡(fan)士(shi)林。
●壹個接(jie)壹個櫃(gui)地(di)安(an)裝母(mu)線(xian),將母線和(he)對應(ying)的分支(zhi)母(mu)線連接(jie)在壹起(qi),栓接(jie)時應(ying)插(cha)入(ru)合適(shi)的墊塊(kuai),用(yong)螺栓(shuan)擰緊。
中(zhong)置(zhi)櫃(gui)接(jie)地(di)裝置(zhi)的安(an)裝。
●將各櫃(gui)的接(jie)地(di)母(mu)線(xian)連(lian)接(jie)在壹起(qi)。
●在櫃(gui)內(nei)連(lian)接(jie)所有需要(yao)接(jie)地(di)的引線。
●將基礎構件(jian)與接(jie)地(di)連(lian)接(jie)起(qi)來,超過(guo)10臺以(yi)上的必(bi)須(xu)有兩(liang)個以(yi)上的接(jie)地(di)線(xian)。
電纜的安(an)裝
●按(an)電纜施工(gong)規範(fan)制(zhi)作電纜頭並將其(qi)與櫃(gui)內(nei)接(jie)線端(duan)連(lian)接(jie)。
●用(yong)電纜夾將電纜固定(ding)在電纜封板上,並緊固(gu)電纜封板。
開關(guan)櫃(gui)安(an)裝結束(shu)後(hou)的檢查(zha)
●當開關(guan)櫃(gui)安(an)裝就(jiu)位(wei)後(hou),清(qing)除櫃(gui)內(nei)的灰塵(chen)雜(za)物(wu),然後(hou)檢(jian)查(zha)堅固(gu)螺(luo)栓有無松動(dong),接(jie)線有無脫落(luo),將斷(duan)路器(qi)在櫃(gui)內(nei)推進拉出並(bing)進行(xing)分(fen)合閘操(cao)作(zuo),觀察(cha)有無異(yi)常(chang)。對(dui)表(biao)計(ji)進行校(xiao)零(ling),根(gen)據線(xian)路圖檢查(zha)二次接(jie)線是(shi)否(fou)正(zheng)確(que)。檢(jian)查(zha)聯(lian)鎖是(shi)否(fou)有效。